Anchor point

For supplementary installation in lift shaft and drive room ceilings without top access

Max. load Centric pull FZ:

  12 20 25 40
Dowel fixing
(1)
2 x anchor dowels
HILTI HST-M 16
(or equiv.),
galvanised
4 x anchor dowels
HILTI HST-M 16
(or equiv.),
galvanised
4 x anchor dowels
HILTI HST-M16
or equiv.),
galvanised
4 x anchor dowels
FISCHER FAZ II M 20
(or equiv.),
galvanisedt
To put under
steel plate (mm)
(2)
2 x washer
17 x 30 x 3
4 x washer
18 x 58 x 5
4 x washer
18 x 58 x 5
4 x washer
18 x 58 x 5
Steel plate (mm)
(3)
100 x 150 x 15 270 x 270 x 15 270 x 270 x 15 250 x 250 x 25
Flat steel anchor
PFEIFER
(4)
RD16 RD20 RD24 RD30
Lifting loop (optional)
PFEIFER
(5)
RD16 RD20 RD24 RD30
Anchor point
Anchor point

Concrete requirements:

  • strength class: ≥ C20/25
  • tensile area/cracked concrete
  • min. element thickness: 160 mm
  • no edge reinforcement
  • dense reinforcement (axial distance of the reinforcement ≤ 15 cm)
Requirements

Edge and center distances as well as other provisions by the manufacturer must be followed exactly. This includes also the transmission of forces within the structural part.

Certification of adequate carrying capacity of the shaft ceiling (thickness, reinforcement, load transmission) is to be provided by the responsible planner.

Furthermore, the supplied instructions for installation and use must be followed strictly.

Product overview
Item No. Carrying capacity (max) kN
00204120001 12
00204200001 20
00204250001 25
00204400001 40

The lifting loop is optional and therefore not included in the scope of delivery. It can, however, be ordered separately.

Installation instructions: The high performance anchors can be used in concrete ceilings of sufficient quality solely. Edge and center distances as well as other provisions by the manufacturer must be followed exactly. This includes also the transmission of forces within the structural part.

Copyright © 2019 Stingl GmbH
This website uses cookies to provide the best possible functionality.
By using this offer, you agree that we may leave cookies on your computer. More information...
OK